日韩国产在线高清一区_色图二区视频在线观看免费视频日韩_欧美日韩国产人成在线观看_720lu在线刺激视频国产_亚洲综合欧美激情_可观看的黄色视频网站_日韩中文字幕二区_波多野结系列无码观看潮_国产av巨制丝袜秘书_老男人久久青草av高清

Precision air conditionin
Guangzhou Granden Electronic Technology Co.,Ltd
Address: Guangzhou city Tianhe District Longkou Road West 77 803room
Phone: 020-87540643
Fax: 020-87540663
Technical support: 13824476182
Website:www.gedz.com.cn
The Current Position >> Home >> Product >>
The secondary power supply prevents thunder device DEHNguard S 275 (DG S 275), DG S 275 FM, DG S3

Product introduction

Germany DEHNguard S 275 (DG S 275), DEHNguard S 275 FM (DG S 275 FM) used for low voltage electrical equipment surge protection for lightning protection partition OB - 1 and subsequent partition. Replace old model DEHNguard T 275 (900 650), DEHNguard T 275 FM (900 680).

Germany DEHNguard S 385 (DG S 385), DEHNguard S 385 FM (DG S 385 FM) used for low voltage electrical equipment surge protection for lightning protection partition OB - 1 and subsequent partition. Replace old model DEHNguard T 385 (900 641) and DEHNguard T 385 FM (900 691).

Function characteristics

? ? general surge protector, the base and insertion module chase flow of zinc oxide varistors, discharge capacity high

? ? "dynamic heat tripping" SPD monitoring device, it is stable and reliable

? ? and Red/Line products series energy coordination

? ? window can display the operating state and fault indicator

? ? multi-function terminal, connecting wire and bus

? ? with module lock device, through the module release button easily replace protection module

? ? through the impact and vibration test, on the basis of the EN 60068-2

Technical parameters

DG S 275 DG S 275 FM

According to the EN 61643-11, SPD level 2 level 2

According to IEC 61643-1, SPD Ⅱ level Ⅱ level

Ac maximum continuous working voltage UC 275 v, 150 v

Dc maximum continuous working voltage UC 350 v, 200 v

Nominal discharge current (8/20 μ s) In 20 ka 40 ka

Maximum discharge current (8/20 μ s) Imax 40 ka 15 ka

Voltage protection level Up acuities were 1.25 kV acuities were 0.7 kV

5 ka, voltage protection level Up acuities 1 kV acuities were 0.55 kV

Response time tA acuities 25 ns acuities 25 ns

Maximum backup fuse 125 a gL/gG 125 a gL/gG

Maximum backup solution wire when short circuit tolerance capacity of 50 karms 50 karms

Transient overvoltage (TOV) UT 350 v / 5 SEC. 350 v / 5 SEC.

Operating temperature range TU - 40 ℃... + 80 ℃ to 40 ℃... + 80 ℃

Working state/fault indicator green/red green/red

Installation conductor section tax (minimum) 1.5 the best callus induction stranded wire/soft line 1.5 the best callus induction stranded wire/soft line

Installation conductor section tax (maximum) and the best callus induction stranded wire / 25 best callus induction soft line and the best callus induction stranded wire / 25 best callus induction soft line

Installation and mmdin rail, on the basis of the EN 60715 35 mmdin rail, on the basis of the EN 60715

Shell material red thermoplastic materials, UL 94-0 red thermoplastic materials, UL 94-0

Protection level IP 20 IP 20

Size 1 mods, DIN 43880 1 mods, DIN 43880

The authentication KEMA, VDE, UL, VdS KEMA, VDE, UL, VdS

Remote signalling contact type - float switch contact

Ac switching capacity - 250 v / 0.5 A

Dc switching capacity - 250 v / 0.1 A; 125 v / 0.2 A; 75 v / 0.5 A

Remote signalling terminal of the cross sectional area - maximum 1.5 the best callus induction stranded wire/soft line