Phone: 020-87540643
Fax: 020-87540663
Technical support: 13824476182
MC model 125 - B/NPE
Rated voltage UN 230 V / 50-60 Hz
Maximum continuous working voltage UC 255 V
Protection class based on VDE 0675 / Part 6 test level based on IEC 61643-1 B class I
Insulation impedance Risol > 100 M W
Protection level UP < 2, 5 kV
Response time tA < 100 ns
Test lightning current numerical (10/350) maximum current Iimp quantity Q energy W/R, according to the international standard IEC 1312-1 (02.95) of the thunder and lightning current parameter 125 kA 62, As 3, 9 MJ/W
Arcing ability 3 100 A eff
Working temperature - 40 ° C up to + 85 ° C
Relative humidity £95%
Protection type IP 20
Connection wire diameter soild/stranded wire gauge 10-50/10-35 mm 2 AWG 8-2
Installation fixed in 35 mm DIN type orbit
Color blue
Structure seal spark gap
Size based on DIN 43880 high wide and deep 100 mm 35 mm 75 mm