Functions and applications: FRD, FLD, FRD2, and FLD2 is used for electronic measurement and control line of the protector, prevent the data line due to lightning or travelling wave caused by the surge overvoltage for related equipment damage. FRD and FLD series of protector is applied to not grounded (asymmetric, suspension) dual system. FRD can be installed in the allow resistance enlarged circuit, if the circuit is not allow resistance increases, the use of FLD. FRD2 and FLD2 series protector is used exclusively and related single system (symmetrical, voltage related). Here also have a series resistance and series inductance choice, if allow resistance increase is selected FRD2, for voltage control device is selected FLD2. Because they are designed for two level protection circuit, so it is also suitable for installation to LPZ1 - LPZ3. FRD and FLD of two stage circuit by gas discharge tube, pressure sensitive resistance and clamp diode composition, has the general flow, clamping time is very short and protection of the low level of characteristics. Installation: OBO FRD and FLD type protector can be installed in any standard switch box or distribution box, simply installed in 35 mm guide rail. No screw terminal reduces the cost of installation.
Performance schedule FRD, FLD protector use advantages
Installed on the 35 mm guide can be installed directly in the power distribution cabinet or switch box
But there is no problem to provide all kinds of voltage user oriented surge protection become possible
No screw pressure welding type terminal is easy to install
Y type circuit, safe for the line, neutral or protection ground to the surge can effectively restrain
FLD/FRD technical parameters
Lightning arrester FRD - 5 FLD - 5 frd2-5 fld2-5-12 FRD FLD - 12 frd2-12 fld2-12 FRD - 24 FLD - 24 frd2-24 fld2-24 FRD - 48 FLD - 48 frd2-48 fld2-48 FRD - 60 FLD - 60 frd2-60 fld2-60 FRD - 110 FLD - 110 frd2-110 fld2-110
LPZ 1-3
Nominal voltage UN maximum sustainable working voltage UC 5 v6v 12 v13. 5 24 v27v 48 v53v 60 v66v 110 v122v
Rated load current FRD, FRD2 IL 0.2 A
Rated load current FLD, FLD2 1.0 A
Nominal discharge current (8/20) In 10 ka
Impact circulation capacity (10/350) Iimp
Voltage protection level Up3-4 acuities 13 v acuities 29 v acuities 51 v acuities 100 v or less 130 v or less 300 v
Each line series resistance FRD, FRD2 R 15 Ω
Each line series inductance FLD, FLD2 L 100 μ H
Connecting cross sectional area connecting line peeling length color material installation size 0.14-2.5 mm26-7 mm light gray, like RAL 7035 polyamide 6 according to DIN EN 50022 installed on the 35 mm guide long 90 mm, 17.8 mm wide, deep 62 mm